DocumentCode :
1761128
Title :
Overcurrent Relays Coordination in Interconnected Networks Using Accurate Analytical Method and Based on Determination of Fault Critical Point
Author :
Alkaran, Davood Solati ; Vatani, Mohammad Reza ; Sanjari, Mohammad Javad ; Gharehpetian, Gevork B. ; Yatim, Abdul Halim
Author_Institution :
Electr. Eng. Dept., Amirkabir Univ. of Technol., Tehran, Iran
Volume :
30
Issue :
2
fYear :
2015
fDate :
42095
Firstpage :
870
Lastpage :
877
Abstract :
Overcurrent relays should be coordinated for different operation conditions in interconnected networks. In addition, the time interval should not reach under the predefined threshold for each pair of primary and backup relays for the faults occurring in the protection zone of the primary relay. An analytical approach is presented in this paper to calculate the impedance matrix of the network in fault condition in order to determine the critical fault point accurately. Overcurrent relays are coordinated by using the presented critical fault point instead of the close-in fault used in previous studies. Simulation results show the accuracy of the proposed method for overcurrent relays coordination in comparison with other methods.
Keywords :
fault diagnosis; impedance matrix; overcurrent protection; power system interconnection; relay protection; accurate analytical method; fault condition; fault critical point determination; impedance matrix; interconnected network; overcurrent relays coordination; primary relay protection zone; time interval; Circuit faults; Equations; Fault currents; Impedance; Mathematical model; Relays; Short-circuit currents; Coordination time interval; critical fault point; optimal coordination; overcurrent relay; primary and backup (P/B) relays;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2014.2330767
Filename :
7057686
Link To Document :
بازگشت