• DocumentCode
    176113
  • Title

    Research on fault location Algorithm for double transmission line on the same tower based on the conductor´s relation of electromagnetic coupling

  • Author

    Kunyi Chen ; Qin Ai ; Shaowu Li ; Dongshan Geng ; Yongchao Yang

  • Author_Institution
    Hubei Univ. for Nat., Enshi, China
  • fYear
    2014
  • fDate
    May 31 2014-June 2 2014
  • Firstpage
    2150
  • Lastpage
    2155
  • Abstract
    The Six-Sequence Fault Components was used for fault location Algorithm of double lines on the same tower commonly. But the Algorithm is greatly influenced by the parameter´s symmetry of transmission line, and particularly, the algorithm will bring bigger error when the conductor transposition is not perfectly. The paper analyzes the error of the fault location Algorithm based on the models of complete transposition and no-complete transposition. According to the results of the above analysis, the paper raises a fault location method by using the electromagnetic coupling relationship between double lines. The PSCAD simulation test indicates that the new method has higher accuracy.
  • Keywords
    electromagnetic coupling; fault location; power transmission faults; transmission network calculations; PSCAD simulation; conductor transposition; double transmission line; electromagnetic coupling; fault location algorithm; noncomplete transposition; parameter symmetry; six-sequence fault component; Electrical resistance measurement; Equations; Fault location; Mathematical model; Measurement uncertainty; Poles and towers; Power transmission lines; double transmission line on the same tower; fault location; no-complete transposition;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Control and Decision Conference (2014 CCDC), The 26th Chinese
  • Conference_Location
    Changsha
  • Print_ISBN
    978-1-4799-3707-3
  • Type

    conf

  • DOI
    10.1109/CCDC.2014.6852523
  • Filename
    6852523