DocumentCode :
1761552
Title :
Asymmetrical Fault Ride Through as Ancillary Service by Constant Power Loads in Grid-Connected Wind Farm
Author :
Jelani, Nadeem ; Molinas, Marta
Author_Institution :
Dept. of Electr. Power Eng., Norwegian Univ. of Sci. & Technol., Trondheim, Norway
Volume :
30
Issue :
3
fYear :
2015
fDate :
42064
Firstpage :
1704
Lastpage :
1713
Abstract :
The introduction of distributed generation (DG) into low voltage (LV) systems demands that the generation system remain grid connected during voltage sags to ensure the operational stability. The DG consisting of fixed speed squirrel cage induction generator (SCIG)-based wind turbines is unable to provide reactive power control and needs a dedicated compensating device. Under asymmetrical grid faults the negative sequence flux circulation in the airgap introduces the torque oscillations that lead to the reduction of lifetime of the generation system. This paper proposes the use of distributed constant power loads (CPLs) for asymmetrical fault ride through (FRT) instead of using a centralized STATCOM. It has also been observed that the compensation of negative sequence voltage improves the performance of SCIG by eliminating the torque ripples. The compensation of positive sequence voltage avoids a possible voltage collapse at the LV distribution level and improves the reliability and stability of the wind farm. Centralized compensation of the asymmetrical grid fault by a STATCOM is compared with the distributed compensation by CPLs. The results suggest that each individual CPL injects lower current for maximum FRT enhancement compared to a dedicated STATCOM.
Keywords :
air gaps; asynchronous generators; compensation; distributed power generation; oscillations; power generation control; power generation faults; power generation reliability; power grids; power supply quality; power system interconnection; power system stability; squirrel cage motors; static VAr compensators; wind power plants; wind turbines; CPL; FRT; LV distribution level; SCIG-based wind turbine; STATCOM; airgap; ancillary service; asymmetrical fault ride through; asymmetrical grid fault; centralized compensation; constant power load; distributed constant power load; distributed generation; generation system lifetime reduction; grid connected wind farm; negative sequence flux circulation; negative sequence voltage compensation; operational stability; reliability; squirrel cage induction generator; stability; torque oscillations; torque ripple elimination; voltage sags; Automatic voltage control; Inductance; Power system stability; Resistance; Torque; Wind farms; Constant power loads (CPLs); distributed energy systems; fault ride through (FRT); power electronics (PEs); reactive power control; voltage source converters (VSCs);
fLanguage :
English
Journal_Title :
Power Electronics, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8993
Type :
jour
DOI :
10.1109/TPEL.2014.2320949
Filename :
6807751
Link To Document :
بازگشت