Title :
Asymmetrical Grid Fault Ride-Through Strategy of Three-Phase Grid-Connected Inverter Considering Network Impedance Impact in Low-Voltage Grid
Author :
Xiaoqiang Guo ; Xue Zhang ; Baocheng Wang ; Weiyang Wu ; Guerrero, Josep M.
Author_Institution :
Dept. of Electr. Eng., Yanshan Univ., Qinhuangdao, China
Volume :
29
Issue :
3
fYear :
2014
fDate :
41699
Firstpage :
1064
Lastpage :
1068
Abstract :
This letter presents a new control strategy of three-phase grid-connected inverter for the positive sequence voltage recovery and negative sequence voltage reduction under asymmetrical grid faults. Unlike the conventional control strategy based on an assumption that the network impedance is mainly inductive, the proposed control strategy is more flexible and effective by considering the network impedance impact, which is of great importance for the high penetration of grid-connected renewable energy systems into low-voltage grids. The experimental tests are carried out to validate the effectiveness of the proposed solution for the flexible voltage support in a low-voltage grid, where the network impedance is mainly resistive.
Keywords :
fault diagnosis; invertors; power grids; renewable energy sources; asymmetrical grid fault ride-through strategy; asymmetrical grid faults; control strategy; flexible voltage support; grid-connected renewable energy systems; low-voltage grid; negative sequence voltage reduction; network impedance impact; positive sequence voltage recovery; three-phase grid-connected inverter; Impedance; Inverters; Low voltage; Power control; Power quality; Reactive power; Voltage control; Fault ride through; flexible voltage support; grid faults; grid-connected inverter;
fLanguage :
English
Journal_Title :
Power Electronics, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8993
Type :
jour
DOI :
10.1109/TPEL.2013.2278030
Filename :
6587279
Link To Document :
بازگشت