• DocumentCode
    1764164
  • Title

    Robustness of Commissioned Coordinated q - V Controller for Multimachine Power Plant

  • Author

    Dragosavac, Jasna ; Janda, Zarko ; Milanovic, Jovica V. ; Arnautovic, Dusan

  • Author_Institution
    Electr. Eng. Inst. Nikola Tesla, Univ. of Belgrade, Belgrade, Serbia
  • Volume
    28
  • Issue
    2
  • fYear
    2013
  • fDate
    41395
  • Firstpage
    1415
  • Lastpage
    1424
  • Abstract
    This paper presents commissioning details of a coordinated reactive power-voltage controller (CQVC) installed in a multimachine steam power plant (SPP). The CQVC regulates reactive power and voltage of a 1992MVA multimachine SPP. After briefly introducing basic control principles and relevant details about the CQVC´s implementation, CQVC parameterization and tuning are thoroughly discussed. Once commissioned,the CQVC performance under various operating conditions is assessed. It is shown that the CQVC successfully maintains an HV busbar voltage and allocates reactive power to participating generators in accordance to their capability. Numerous CQVC responses recorded at the site are presented to demonstrate controller´s performance under normal and extreme plant and network operating conditions.
  • Keywords
    reactive power control; steam power stations; voltage control; CQVC parameterization; HV busbar voltage; apparent power 1992 MVA; commissioned coordinated Q-V controller; commissioning details; coordinated reactive power-voltage controller; multimachine steam power plant; network operating conditions; plant operating conditions; Generators; Power generation; Reactive power; Robustness; Sensitivity; Voltage control; Voltage measurement; Coordinated voltage control; D-diagram; reactive power control; robustness;
  • fLanguage
    English
  • Journal_Title
    Power Systems, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    0885-8950
  • Type

    jour

  • DOI
    10.1109/TPWRS.2012.2227512
  • Filename