DocumentCode
1764164
Title
Robustness of Commissioned Coordinated q - V Controller for Multimachine Power Plant
Author
Dragosavac, Jasna ; Janda, Zarko ; Milanovic, Jovica V. ; Arnautovic, Dusan
Author_Institution
Electr. Eng. Inst. Nikola Tesla, Univ. of Belgrade, Belgrade, Serbia
Volume
28
Issue
2
fYear
2013
fDate
41395
Firstpage
1415
Lastpage
1424
Abstract
This paper presents commissioning details of a coordinated reactive power-voltage controller (CQVC) installed in a multimachine steam power plant (SPP). The CQVC regulates reactive power and voltage of a 1992MVA multimachine SPP. After briefly introducing basic control principles and relevant details about the CQVC´s implementation, CQVC parameterization and tuning are thoroughly discussed. Once commissioned,the CQVC performance under various operating conditions is assessed. It is shown that the CQVC successfully maintains an HV busbar voltage and allocates reactive power to participating generators in accordance to their capability. Numerous CQVC responses recorded at the site are presented to demonstrate controller´s performance under normal and extreme plant and network operating conditions.
Keywords
reactive power control; steam power stations; voltage control; CQVC parameterization; HV busbar voltage; apparent power 1992 MVA; commissioned coordinated Q-V controller; commissioning details; coordinated reactive power-voltage controller; multimachine steam power plant; network operating conditions; plant operating conditions; Generators; Power generation; Reactive power; Robustness; Sensitivity; Voltage control; Voltage measurement; Coordinated voltage control; D-diagram; reactive power control; robustness;
fLanguage
English
Journal_Title
Power Systems, IEEE Transactions on
Publisher
ieee
ISSN
0885-8950
Type
jour
DOI
10.1109/TPWRS.2012.2227512
Filename
6389744
Link To Document