DocumentCode
1765404
Title
DC Grid Control Through the Pilot Voltage Droop Concept—Methodology for Establishing Droop Constants
Author
Berggren, Bertil ; Linden, Kerstin ; Majumder, Ritwik
Author_Institution
ABB Corp. Res., Västerås, Sweden
Volume
30
Issue
5
fYear
2015
fDate
Sept. 2015
Firstpage
2312
Lastpage
2320
Abstract
Converter control is an important aspect of voltage-source-converter high-voltage dc (VSC-HVDC) based multi-terminal dc grids. Variants of power drooped against dc voltage control have previously been proposed for this purpose. However, there is at this time no clear methodology available on how to select the size of the droop constants for distributing a power mismatch, following, e.g., a converter trip, on several converters. This paper proposes a methodology for establishing droop constants for a variant of power drooped against dc voltage called pilot voltage droop control. The methodology is derived from the basic control laws in a straight forward fashion and the accuracy is exemplified by time domain simulations in Digsilent´s Powerfactory platform.
Keywords
DC-DC power convertors; voltage control; DC grid control; converter control; dc voltage control; droop constants; multi-terminal DC grids; pilot voltage droop concept; voltage-source-converter high-voltage DC; Context; Current measurement; Frequency control; Steady-state; Valves; Voltage control; Voltage measurement; dc grid; droop control; high-voltage dc; voltage source converters;
fLanguage
English
Journal_Title
Power Systems, IEEE Transactions on
Publisher
ieee
ISSN
0885-8950
Type
jour
DOI
10.1109/TPWRS.2014.2360585