• DocumentCode
    1766369
  • Title

    Comparative aging characteristics between a high oleic natural ester dielectric liquid and mineral oil

  • Author

    Singha, Santanu ; Asano, Roberto ; Frimpong, George ; Claiborne, C. Clair ; Cherry, Don

  • Author_Institution
    Corp. Res., ABB AB, Vasteras, Sweden
  • Volume
    21
  • Issue
    1
  • fYear
    2014
  • fDate
    41671
  • Firstpage
    149
  • Lastpage
    158
  • Abstract
    This paper presents a comparative evaluation of the aging characteristics between a high oleic natural ester dielectric liquid (HONE) and mineral oil based on an accelerated single-temperature thermal aging experiment at 150°C for a period of 3000 hours. The important physical (e.g., viscosity, moisture content, acidity) and dielectric (e.g., power factor, alternating current (AC) dielectric breakdown) properties of both the oils were measured and analyzed at different aging intervals. As expected, results show differences in aging behaviors between mineral oil and the natural ester liquid. The relative moisture content in HONE had stable and lower values during the aging duration as compared to the case of mineral oil, where the relative moisture content increased with the aging duration. Further, unlike the observations in mineral oil, the power factor (PF) and acidity of HONE increased drastically with increasing aging times. The most relevant observation made from this study was that in spite of this significant increase in the PF and acidity of HONE with aging, its AC dielectric breakdown voltage was quite stable, which is not observed in the case of mineral oil. This indicates that for natural ester liquids, higher values of PF (or dielectric dissipation factor) and/or acidity due to aging may not necessarily give a true picture on the dielectric performance of the ester. It is therefore important to note here that the threshold limits of some of the diagnostic parameters which are already established for mineral oil do not apply for ester liquids.
  • Keywords
    ageing; dielectric liquids; electric breakdown; power factor; power transformer insulation; transformer oil; AC dielectric breakdown voltage; HONE acidity; PF; accelerated single-temperature thermal aging; comparative aging characteristics; dielectric dissipation factor; dielectric properties; high oleic natural ester dielectric liquid; mineral oil; power factor; relative moisture content; temperature 150 degC; time 3000 hour; transformer oil; Aging; Dielectric liquids; Liquids; Minerals; Moisture; Oil insulation; Power transformer insulation; Natural ester; acidity; diagnostics; dielectric; insulating; moisture; power factor; thermal aging; transformer;
  • fLanguage
    English
  • Journal_Title
    Dielectrics and Electrical Insulation, IEEE Transactions on
  • Publisher
    ieee
  • ISSN
    1070-9878
  • Type

    jour

  • DOI
    10.1109/TDEI.2013.003713
  • Filename
    6740735