• DocumentCode
    1770760
  • Title

    Utilization of DFIG on an islanded power generation and distribution system

  • Author

    Rossi, Roberto

  • Author_Institution
    R. Rossi & Assoc., Perth, WA, Australia
  • fYear
    2014
  • fDate
    11-13 June 2014
  • Firstpage
    155
  • Lastpage
    160
  • Abstract
    The utilization of wind generation equipment, such as DFIGs (double fed induction generators), interconnected to islanded power generation and distribution systems is investigated in order to determine their effects on the overall system operating characteristics and stability. The use of a stable power station (with high speed machines) will be critical in achieving fast and reliable transient response to network events, in particular, when large transient loads are expected on a continuous basis, i.e., industrial mining and mineral processing equipment. Simulation results of this paper assist in understanding how small power stations and wind generation equipment respond to large transients in an islanded network. In particular, detailed simulations and analyses will be presented on impacts of distributed wind generation units (1.5 MW DFIG) on the stability of a small weak network. The novelty of this paper is on detailed analyses and simulation of weak, islanded networks with interconnects DFIG´s including their impacts on system stability under various transient operating conditions.
  • Keywords
    asynchronous generators; distribution networks; electric power generation; power system interconnection; power system transient stability; transient response; DFIG interconnection; continuous basis; distributed wind generation units; distribution system; double fed induction generators; high speed machines; industrial mining; islanded power generation; mineral processing equipment; power 1.5 MW; small power stations; system stability; transient loads; transient response; wind generation equipment; Equations; Load modeling; Power system stability; Stability analysis; Transient analysis; Wind power generation; CFCT (critical fault clearing time); DFIG (double fed induction generator); DG (distributed generation); DOL (direct on line); Grid System; VVVF (variable voltage variable frequency); Weak Network;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electric Power Quality and Supply Reliability Conference (PQ), 2014
  • Conference_Location
    Rakvere
  • Print_ISBN
    978-1-4799-5020-1
  • Type

    conf

  • DOI
    10.1109/PQ.2014.6866801
  • Filename
    6866801