• DocumentCode
    1770837
  • Title

    Influence of neutral grounding method on voltage unbalance in 10 kV network with cable lines and overhead lines

  • Author

    Kochura, Danila ; Tsivilyov, Igor ; Sarin, Leonid

  • Author_Institution
    Int. Relations & Eng. Dept., BOLID LLC, Novosibirsk, Russia
  • fYear
    2014
  • fDate
    11-13 June 2014
  • Firstpage
    359
  • Lastpage
    362
  • Abstract
    The paper presents the results of experimental and computational investigations of power quality in the 10 kV network with different types of neutral grounding. It is shown that parameters of equipment, connected to the neutral point, have a significant impact on power quality in the field of voltage unbalance, up to deviation from standard values. The area of proper power quality in the field of zero sequence voltage unbalance for 10 kV network is determined. It depends on the ratio of overhead lines and cable lines capacitive current, on the type of neutral grounding. It is found out that power quality in the field of zero sequence voltage unbalance may be significantly improved by connection of additional resistance into a zero sequence circuit of the network.
  • Keywords
    distribution networks; earthing; power cables; power overhead lines; power supply quality; cable lines; capacitive current; neutral grounding; overhead lines; power quality; voltage 10 kV; zero sequence voltage unbalance; Capacitance; Coils; Grounding; Power quality; Resistance; Resistors; Standards; electrical equipment industry; power distribution; power quality; power system analysis computing; power system measurement;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electric Power Quality and Supply Reliability Conference (PQ), 2014
  • Conference_Location
    Rakvere
  • Print_ISBN
    978-1-4799-5020-1
  • Type

    conf

  • DOI
    10.1109/PQ.2014.6866841
  • Filename
    6866841