Title :
Density monitoring of high voltage SF6 circuit breakers
Author :
Cheetham, Peter ; Hellany, A.
Author_Institution :
Sch. of Comput., Eng. & Math., Univ. of Western Sydney, Sydney, NSW, Australia
Abstract :
As a circuit breaker ages it becomes more susceptible to SF6 leaks. Retrofitting density monitoring equipment to existing circuit breakers allows for the early detection of a SF6 leak before a low pressure alarm is raised. This report analyses different aspects of density monitoring which need to be considered to successfully retrofit a SF6 circuit breaker with density monitoring equipment. These aspects include sampling rate, what type of transducer to use and how to interpret the density measurements to detect SF6 leaks.
Keywords :
SF6 insulation; circuit breakers; density measurement; maintenance engineering; SF6 circuit breaker; SF6 leaks; density measurements; density monitoring equipment; low pressure alarm; retrofitting; Circuit breakers; Density measurement; Fluctuations; Monitoring; Sulfur hexafluoride; Temperature measurement; Transducers; SF6; circuit breaker; density monitoring;
Conference_Titel :
Electrical Insulation Conference (EIC), 2014
Conference_Location :
Philadelphia, PA
Print_ISBN :
978-1-4799-2787-6
DOI :
10.1109/EIC.2014.6869354