DocumentCode :
1773281
Title :
Analysis of the arcing process in on-load tap changers by measuring the acoustic signature
Author :
Bhuyan, Ranjan ; Mor, Armando ; Morshuis, P. ; Montanari, Gian ; Erinkveld, Wim
Author_Institution :
Delft Univ. of Technol., Delft, Netherlands
fYear :
2014
fDate :
8-11 June 2014
Firstpage :
193
Lastpage :
197
Abstract :
Power transformers are fundamental parts of the power system. In order to keep the availability of power systems high, the reliability of a transformer, in all its parts, must be assured. This requires also paying attention to the reliability of the tap changer, as tap changer failures are major causes of power transformer breakdown. This paper focuses on the development of acoustic diagnostics for on-load tap changers (OLTC). A selector switch-type tap changer was used to detect and characterize different defects that may ultimately lead to a tap changer failure. Among other techniques, acoustic diagnostic was considered first because it is a method which can work online without affecting in any way the normal operation of a power transformer. Special emphasis was dedicated to recreate the arcing conditions in a tap changer. Arcing inside the tap changer chamber is unavoidable, but excessive arcing leads to a multitude of problems, so that efforts have been made to detect acoustically the signature of the arcing phenomenon. In order to have both flexibility and control over the experimental parameters, the tests were conducted on two sets of test objects, i.e. a model and a small-size tap changer. Focus was made to the type of defects that pose the most imminent threat to the tap changer operation, and the most appropriate methods of signal acquisition and processing were singled out. It is shown that these defects can be recognized based on their specific acoustic signature.
Keywords :
acoustic signal detection; acoustic signal processing; arcs (electric); failure analysis; on load tap changers; power transformer protection; power transformer testing; OLTC; acoustic diagnostics; acoustic signature; arcing conditions; arcing process; on-load tap changers; power systems; power transformer breakdown; power transformers; selector switch-type tap changer; signal acquisition; signal processing; tap changer failure; transformer reliability; Acoustic measurements; Acoustic pulses; Frequency measurement; Maintenance engineering; On load tap changers; acoustic detection; acoustic signature; arcing phenomenon; on-load tap changer;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation Conference (EIC), 2014
Conference_Location :
Philadelphia, PA
Print_ISBN :
978-1-4799-2787-6
Type :
conf
DOI :
10.1109/EIC.2014.6869374
Filename :
6869374
Link To Document :