Abstract :
Some place requires for highly power supply reliability, common feeder automation solution can´t meet the requirements, so, we need to restudy the feeder automation solution. This paper involves the FA scheme based on fault status differential protection, by using optical fiber communication to achieve the selectivity of protection, fault location, isolation, power recovery. Finally, through the analysis of a system fault conditions in open-loop and closed-loop operation, the result shows that system could remove fault quickly one-time, breakers no need reclose more times, the impact on the system and power distribution equipment is reduced, non-fault section no need power cutting, greatly improving the quality of power supply.
Keywords :
fault diagnosis; power supply quality; power system protection; power system reliability; closed-loop operation; fault location; fault status differential protection; feeder automation solution; open-loop operation; optical fiber communication; power distribution equipment; power recovery; power supply quality; power supply reliability; system fault conditions; Abstracts; Automation; Current measurement; Wiring; Fault Isolation; Fault Location; Fault Remove; Fault Status Differential Protection; Feeder Automatnin; Quality Of Power Supply;
Conference_Titel :
Electricity Distribution (CICED), 2014 China International Conference on
Conference_Location :
Shenzhen
DOI :
10.1109/CICED.2014.6991717