Title :
Analysis of line parameter symmetry and phase sequence arrange concerning four circuits on one tower
Author :
Li Tiangang ; Long Mao ; An Ranran ; Tang Cui ; Wang Yi ; He Maohui
Author_Institution :
Electr. Power Res. Inst., Guangdong Power Grid Corp., Guangzhou, China
Abstract :
Asymmetry of line parameter has great impact on the safe operation of the power system and its relay protection´s performance, while different phase sequence arrange will affect the symmetry of transmission lines. A calculation method of sequence impedance parameter is firstly put for ward, concerning four circuits on one tower. On this basis, the paper analyzes the effect on line parameter symmetry of different phase sequence arrange by calculating single-sequence component unbalanced degree and composite-sequence component unbalanced degree. Further, superior phase sequence arrange schemes of same-voltage and mixed -voltage four circuits on one tower is proposed. The conclusion will contribute to the standard design of four circuits on one tower.
Keywords :
poles and towers; relay protection; transmission network calculations; composite-sequence component unbalanced degree; line parameter asymmetry; mixed-voltage four circuits; power system; relay protection performance; same-voltage four circuits; sequence impedance parameter; single-sequence component unbalanced degree; superior phase sequence arrange schemes; Abstracts; Bismuth; Poles and towers; Wires; calculation of line sequence parameter; four circuits on one tower; phase sequence arrange; unbalanced degree;
Conference_Titel :
Electricity Distribution (CICED), 2014 China International Conference on
Conference_Location :
Shenzhen
DOI :
10.1109/CICED.2014.6991797