    Influence of the injected current on dynamic contact resistance measurements of HV circuit breakers

  • Author

    Cheng Tingting ; Zhu Wenjun ; Jin Guangyao ; Yang Zhiyong ; Wensheng Gao

  • Author_Institution
    Dept. of Electr. Eng., Tsinghua Univ., Beijing, China
  • fYear
    2014
  • fDate
    23-26 Sept. 2014
  • Firstpage
    1477
  • Lastpage
    1481
  • Abstract
    Dynamic contact resistance measurement (DRM) is an effective technique for assessing the condition of power circuit breaker main contacts and arcing contacts. However, DRMs are easily affected by measurement condition, and they vary widely with changes of measurement condition, which is likely to lead to misjudgments. The problem can be relieved by increasing the injected current value. The proposed paper researched the influence of the dc injected current on dynamic contact resistance, and discovered that the average main contact resistance, the average arcing contact resistance, and the standard deviation of DRM curve decreased with the increase in the current value. At the same time, the reproducibility of parameters above improved. Besides, this paper also proposes a proper DRM strategy for the tested breaker.
  • Keywords
    circuit breakers; circuit-breaking arcs; contact resistance; electric resistance measurement; switchgear testing; DC injected current; DRM; HV circuit breaker; average arcing contact resistance; dynamic contact resistance measurement; Abstracts; Current measurement; Integrated circuit reliability; Power measurement; Resistance; Time measurement; DRM; Dynamic contact resistance measurement; Electrical current; High voltage circuit breaker;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electricity Distribution (CICED), 2014 China International Conference on
  • Conference_Location
    Shenzhen
  • Type

    conf

  • DOI
    10.1109/CICED.2014.6991951
  • Filename
    6991951