Analysis for the abnormal growth of bushing dielectric loss in a 500KV transformer
Author :
Chen Xiao ; Zhang Bin ; Huang Wei-Zhao
Author_Institution :
Shenzhen Power Supply Co., Shenzhen, China
fYear :
2014
fDate :
23-26 Sept. 2014
Firstpage :
1574
Lastpage :
1577
Abstract :
In the preventive test of a imported 500kV transformer, defects are found in the neutral bushing and mid-voltage side bushing that the dielectric loss grows abnormally. The defective bushings are analysis with the method of dielectric loss comparison, high voltage dielectric loss test, frequency domain dielectric spectrum analysis. And the analysis result shows, the abnormal growth is caused by the defect that the capacitor core is not fully dried. The moisture permeates gradually and increases the power loss. Discovery of this defect lowers the risk of internal insulation breakdown caused by the large power loss and high temperature. Provide a new idea for defect judgment, and avoid long time power failure caused by malfunction of the bushing. It provides reference for the same bushing malfunction in the future.
Keywords :
bushings; dielectric losses; electric breakdown; frequency-domain analysis; moisture; power system reliability; power transformer insulation; bushing dielectric loss abnormal growth analysis; bushing malfunction; dielectric loss comparison; frequency domain dielectric spectrum analysis; high voltage dielectric loss test; internal insulation breakdown risk; long time power failure avoidance; moisture; power loss; transformer; voltage 500 kV; Abstracts; Capacitance; Cleaning; Dielectric losses; Power transformer insulation; Abnormal Growth; Bushing; Dielectric loss; Moisture; Transformer;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electricity Distribution (CICED), 2014 China International Conference on
Conference_Location :
Shenzhen
Type :
conf
DOI :
10.1109/CICED.2014.6991971
Filename :
6991971
Link To Document :
بازگشت