DocumentCode
1775026
Title
Evaluation of insulation of H.V. Bushing—Online monitoring tgδ of a 500kV bushing
Author
Yi Li ; Mingjun Cheng ; Huaping Xu ; Shengjie Huang ; West, Herschel J.
Author_Institution
EHV Transm. & Substation Co., Guiyang Branch, China Southern Power Grid Co., Ltd., Guiyang, China
fYear
2014
fDate
1-5 June 2014
Firstpage
303
Lastpage
306
Abstract
This paper represents a series of online monitoring data from a 500kV bushing on a converter station´s transformer. An online monitoring system with a novel tgd measuring method has been successfully used for bushing tgd supervision. Long term data acquisition is evaluated for the insulation integrity of the bushing. It shows that bushing tgδ depends on its temperature/voltage intersect influence during operation. The largest bushing tgd occurred at the highest voltage and the lower temperatures. A further study of the temperature/voltage intersect influence on bushings need to be scheduled.
Keywords
bushings; computerised monitoring; power transformer insulation; H.V. bushing insulation; bushing tgd supervision; converter station transformer; insulation integrity; long term data acquisition; online monitoring data; online monitoring system; voltage 500 kV; Grounding; Instruments; Insulators; Monitoring; Temperature measurement; Temperature sensors; Bushing; Insulation; Intersect influence; Online monitoring; Temperature; tgδ;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulating Materials (ISEIM), Proceedings of 2014 International Symposium on
Conference_Location
Niigata
Type
conf
DOI
10.1109/ISEIM.2014.6870779