• DocumentCode
    1775026
  • Title

    Evaluation of insulation of H.V. Bushing—Online monitoring tgδ of a 500kV bushing

  • Author

    Yi Li ; Mingjun Cheng ; Huaping Xu ; Shengjie Huang ; West, Herschel J.

  • Author_Institution
    EHV Transm. & Substation Co., Guiyang Branch, China Southern Power Grid Co., Ltd., Guiyang, China
  • fYear
    2014
  • fDate
    1-5 June 2014
  • Firstpage
    303
  • Lastpage
    306
  • Abstract
    This paper represents a series of online monitoring data from a 500kV bushing on a converter station´s transformer. An online monitoring system with a novel tgd measuring method has been successfully used for bushing tgd supervision. Long term data acquisition is evaluated for the insulation integrity of the bushing. It shows that bushing tgδ depends on its temperature/voltage intersect influence during operation. The largest bushing tgd occurred at the highest voltage and the lower temperatures. A further study of the temperature/voltage intersect influence on bushings need to be scheduled.
  • Keywords
    bushings; computerised monitoring; power transformer insulation; H.V. bushing insulation; bushing tgd supervision; converter station transformer; insulation integrity; long term data acquisition; online monitoring data; online monitoring system; voltage 500 kV; Grounding; Instruments; Insulators; Monitoring; Temperature measurement; Temperature sensors; Bushing; Insulation; Intersect influence; Online monitoring; Temperature; tgδ;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulating Materials (ISEIM), Proceedings of 2014 International Symposium on
  • Conference_Location
    Niigata
  • Type

    conf

  • DOI
    10.1109/ISEIM.2014.6870779
  • Filename
    6870779