DocumentCode :
1775163
Title :
The optimization of 500 kV breaker failure protection
Author :
Yu Jiang ; Zhou Hongyang ; Chen Zhaohui ; Li Jie ; Li YiQuan ; Zhang Shaofan
fYear :
2014
fDate :
23-26 Sept. 2014
Firstpage :
1755
Lastpage :
1758
Abstract :
With the development of electric network, fault Critical Clearing Time (CCT) becomes shorter and shorter. Breaker failure influence to system stability more and more deeply. The main factors of fault clearing time includes protection releasing time, inherent breaker opening time, arc extinction time, current element returning time. Distribution and maximum of each component are analysed. Setting and logic optimization of breaker failure protection is submitted. Optimized setting had been used in some key station in CSG.
Keywords :
circuit breakers; optimisation; power system protection; CSG; arc extinction time; breaker failure protection; current element returning time; fault critical clearing time; inherent breaker opening time; protection releasing time; voltage 500 kV; Abstracts; Automation; Companies; Delay effects; Optimization; Time factors; Breaker failure; TA Tailing; arcing time; mechanical movement time;