DocumentCode
1777603
Title
Design of UHVDC earth electrode
Author
Yuan Shichao ; Gong Xiangyang ; Luo Yi
Author_Institution
Ningbo Electr. Power Bur., Ningbo, China
fYear
2014
fDate
20-22 Oct. 2014
Firstpage
2217
Lastpage
2220
Abstract
Based on the differences between UHVDC system and HVDC system, this paper introduces the new safety requirements of UHVDC earth electrode, elaborates the design process of UHVDC earth electrode and emphatically analyzes two design requirements: the maximum allowable step potential and the maximum allowable temperature. Analysis indicates that step potential in previous HVDC earth electrode design is quite strict and not suitable for the situation, the new standard is proposed. In addition, the body size of UHVDC earth electrode is unlike the previous HVDC earth electrode mainly limited by thermal stability, but is decided by step potential limits.
Keywords
HVDC power transmission; earth electrodes; thermal stability; UHVDC earth electrode; UHVDC system; maximum allowable step potential; maximum allowable temperature; safety requirements; step potential limits; thermal stability; Earth; Electric potential; Electrodes; HVDC transmission; Land surface temperature; Thermal stability; UHVDC earth electrode; design of earth electrode; earth electrode thermal stability; the maximum allowable step potential;
fLanguage
English
Publisher
ieee
Conference_Titel
Power System Technology (POWERCON), 2014 International Conference on
Conference_Location
Chengdu
Type
conf
DOI
10.1109/POWERCON.2014.6993721
Filename
6993721
Link To Document