A measurement technique to identify and locate partial discharge in transformer with AE and HFCT
Author :
Fuangsoongnern, Urairat ; Plueksawan, Winai ; Tikakosol, Kittimasak
Author_Institution :
Fac. of Eng., Kasetsart Univ., Bangkok, Thailand
fYear :
2014
fDate :
20-23 May 2014
Firstpage :
108
Lastpage :
113
Abstract :
This paper proposes a measurement technique to identify and locate the occurrence of partial discharge (PD) in the insulation of high voltage oil immersed distribution transformer and dry type distribution transformers. With reference to IEEE Std. C57.127-2007, four acoustic transducers of type PD-TP500A were used to locate partial discharge and one HFCT (High frequency current transducer) was used to identify partial discharge. This technique could correctly identify and locate the source of partial discharge occurring at any position in a distribution transformer. The result of the findings enabled us to prevent damage and deploy preventive maintenance measure on the distribution transformer in time.
Keywords :
IEEE standards; acoustic emission; acoustic transducers; partial discharge measurement; power transformer insulation; transformer oil; AE; HFCT; IEEE Std. C57.127-2007; PD-TP500A; acoustic emission; acoustic transducer; dry type distribution transformer; high frequency current transducer; high voltage oil immersed distribution transformer insulation; measurement technique; partial discharge identification; partial discharge localization; transformer damage prevention; Frequency measurement; Intelligent sensors; Oil insulation; Partial discharges; Power transformer insulation; Acoustic Emission; High Frequency Current Transducer; Oil Type Transformer; Partial Discharge;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Innovative Smart Grid Technologies - Asia (ISGT Asia), 2014 IEEE
Conference_Location :
Kuala Lumpur
Type :
conf
DOI :
10.1109/ISGT-Asia.2014.6873773
Filename :
6873773
Link To Document :
بازگشت