DocumentCode :
1778277
Title :
Secondary reserve limitation to wind power penetration in the Spanish power system
Author :
Fernandez-Bernal, F. ; Egido, Ignacio ; Lobato, Enrique
Author_Institution :
Sch. of Eng., Univ. Pontificia Comillas, Madrid, Spain
fYear :
2014
fDate :
20-23 May 2014
Firstpage :
147
Lastpage :
152
Abstract :
The increasing demand coverage by wind power is posing new challenges to the operation of power systems. In this paper the effect on secondary reserve necessary to overcome the added uncertainty is analyzed. Maximum wind power demand coverage, limited by the secondary reserve value requirement, is assessed. The Spanish power system is used for numerical application using real data. Maximum demand coverage of around 60%-80% is possible without compromising secondary reserve value. An increase of 70%-200% in secondary reserve is expected for a demand coverage of around 60%. Some dynamic performance considerations on the secondary regulation are given for the Spanish case.
Keywords :
demand side management; wind power plants; Spain; dynamic performance; maximum wind power demand coverage; power system operation; secondary reserve limitation; wind power system penetration; Asia; Production; Smart grids; Uncertainty; Wind forecasting; Wind power generation; Wind power generation; ancillary services; load frequency control; secondary reserve;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Innovative Smart Grid Technologies - Asia (ISGT Asia), 2014 IEEE
Conference_Location :
Kuala Lumpur
Type :
conf
DOI :
10.1109/ISGT-Asia.2014.6873780
Filename :
6873780
Link To Document :
بازگشت