Abstract :
Power transformers are the most expensive equipment in a substation. Hence, to assess the health of transformers several diagnostic methods have been proposed. In this regard Frequency Response Analysis (FRA) is considered to be one of the important diagnostic tools for determination of winding movement and coil failure. The present work reports a detailed analysis of Frequency Response (FR) and Coherence Function (CF) estimation of the valve winding (HVDC winding) of a 500 kV HVDC converter transformer. The star connected winding is theoretically simulated by distributed inductances and capacitances and an equivalent electric current is derived. A standard impulse voltage is applied at the HV terminal and the current is calculated in the grounded neutral winding. By varying the radius of the coil and duct thickness the new parameters and associated neutral currents are calculated. The currents so obtained are subjected to Fast Fourier Transform (FFT) and CF analysis. A comparison of results obtained provides a relationship between FRA and CF for different radii and duct thicknesses simulating radial and axial movement.
Keywords :
HVDC power convertors; coils; earthing; failure analysis; fast Fourier transforms; fault diagnosis; frequency response; transformer windings; CF analysis; CF estimation; FFT analysis; FR estimation; FRA; HV terminal; HVDC converter transformer; HVDC winding; axial movement detection; coherence function estimation; coherence function method; coil failure; coil radius; diagnostic method; distributed capacitance; distributed inductance; duct thickness; equivalent electric current; fast Fourier transform; frequency response analysis; grounded neutral winding; high voltage power transformer health; radial movement detection; standard impulse voltage; substation; valve winding movement; voltage 500 kV; Circuit faults; Coherence; Coils; Ducts; Power transformer insulation; Windings; Coherence Function; Converter Transformer; Frequency Response Analysis (FRA); Neutral Currents; Power Transformer Diagnostics;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation and Dielectric Phenomena (CEIDP), 2014 IEEE Conference on
Conference_Location :
Des Moines, IA
Type :
conf
DOI :
10.1109/CEIDP.2014.6995844
Filename :
6995844
Link To Document :
بازگشت