Study of generator modes effects on electric power quality and air gap
Author :
Elmanis-Helmanis, Rihards ; Griscenko, Marina
Author_Institution :
Riga Tech. Univ., Riga, Latvia
fYear :
2014
fDate :
14-14 Oct. 2014
Firstpage :
204
Lastpage :
209
Abstract :
The study examines hydroelectric power generator characteristics, voltage quality, air gap and vibration, in different operational modes - no-load mode, 90, 45, 10 MW load, 90 MW load with -50 MVAr to 20 MVAr reactive power and synchronous compensator mode with 0 MW-20 MW active power and synchronous compensator mode with -10 MVAr to -60 MVAr reactive power. Developed framework for power quality and air gap measurements assessment of hydropower generator shows that correlation exists between voltage, air gap and vibration characteristics. Analysis and comparison of different operational modes are performed to identify, which modes are important during diagnostics of machine condition in hydroelectric generators.
Keywords :
hydroelectric generators; machine insulation; power supply quality; vibrations; air gap; air gap measurements assessment; electric power quality; generator modes effects; hydroelectric power generator characteristics; hydropower generator; machine condition diagnostics; no-load mode; reactive power mode; synchronous compensator mode; vibration characteristics; voltage quality; Generators; Power measurement; Rotors; Stator cores; Vibration measurement; Vibrations; Air gap; hydroelectric power generation; power quality; vibrations;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power and Electrical Engineering of Riga Technical University (RTUCON), 2014 55th International Scientific Conference on
Conference_Location :
Riga
Print_ISBN :
978-1-4799-7460-3
Type :
conf
DOI :
10.1109/RTUCON.2014.6998186
Filename :
6998186
Link To Document :
بازگشت