DocumentCode :
1785672
Title :
The effect of various types of distributed generations on ferroresonance
Author :
Esmaeili, M. ; Rostami, Mohamad ; Gharehpetian, G.B.
Author_Institution :
MScDept. of Electr. Eng., Shahed Univ., Tehran, Iran
fYear :
2014
fDate :
20-22 May 2014
Firstpage :
803
Lastpage :
807
Abstract :
This paper focuses on ferroresonance phenomenon in distribution networks in the presence of Distributed Generation (DG) after islanding. The effect of three different types of DGs (i.e., induction machine based DG, synchronous machine based DG and inverter based DGs) are analyzed and studied. The studies are performed based on the simulations using the PSCAD/EMTDC software. This study has shown that both induction and synchronous based DGs are susceptible to ferroresonance phenomenon occurrence. Inverter based DGs have best operation encounter with ferroresonance.
Keywords :
asynchronous machines; distributed power generation; distribution networks; ferroresonance; invertors; synchronous machines; PSCAD/EMTDC software; distributed generations; distribution networks; ferroresonance; induction machine based DG; inverter based DG; islanding; synchronous machine based DG; Capacitance; Circuit faults; Distributed power generation; Ferroresonance; Harmonic analysis; Inverters; Surges; Distributed Generation; Ferroresonance; Island; Overvoltages;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Engineering (ICEE), 2014 22nd Iranian Conference on
Conference_Location :
Tehran
Type :
conf
DOI :
10.1109/IranianCEE.2014.6999646
Filename :
6999646
Link To Document :
بازگشت