Feasibility Study on Plastic Pipe Used in Simple Automatic Sprinkler System
Author :
Xiu-Ji Guo ; Zheng Fang ; Juan-Juan Chen ; Jun-Heng Wang
Author_Institution :
Civil Eng. Sch., Wuhan Univ., Wuhan, China
fYear :
2014
fDate :
25-26 Oct. 2014
Firstpage :
260
Lastpage :
263
Abstract :
The simple automatic sprinkler system, with the characteristics of small investment and simple construction, is widely used in various small existing buildings that have high risk of fire. In this study, experiments were conducted to analyze the feasibility of using plastic pipe in the simple automatic sprinkler system. The results of the study conclude that hot-water plastic pipe can tolerate the temperatures of the initial phase of fire in fast response sprinklers.
Keywords :
fires; flameproofing; pipes; automatic sprinkler system; fire phase; fire risk; hot-water plastic pipe; Buildings; Combustion; Fires; Paints; Plastics; Temperature control; fire test; plastic pipe; simple automatic sprinkler system;