DocumentCode
1797684
Title
A new simulation method of switching overvoltage on shunt capacitors
Author
Liqun Shang ; Senfeng Zhang
Author_Institution
Sch. of Electr. & Control Eng., Xi´an Univ. of Sci. & Technol., Xi´an, China
fYear
2014
fDate
15-17 Nov. 2014
Firstpage
215
Lastpage
219
Abstract
Shunt capacitor banks are widely used in reactive power compensation, but the operating over voltage caused by the frequent operation of shunt capacitors would damage the insulated equipment and affect the reliability of power system. For simulating the switching off over voltage of shunt capacitors by vacuum circuit breakers, the model by adding a normal closed breaker to simulate restrike over voltage of breaker was proposed in this paper, then the restrike over voltage are calculated by using the proposed model, and the effects of limiting restrike over voltage of shunt capacitor by using MOA arrester are simulated. Simulation results are consistent with theory analysis.
Keywords
arresters; overvoltage protection; power capacitors; power system reliability; reactive power; vacuum circuit breakers; MOA arrester; overvoltage switching; power system reliability; reactive power compensation; shunt capacitors; vacuum circuit breakers; Arresters; Capacitance; Capacitors; Insulation; Shunts (electrical); Switches; Voltage control; MOA arrester; Shunt capacitor banks; restrike overvoltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Systems and Informatics (ICSAI), 2014 2nd International Conference on
Conference_Location
Shanghai
Print_ISBN
978-1-4799-5457-5
Type
conf
DOI
10.1109/ICSAI.2014.7009288
Filename
7009288
Link To Document