• DocumentCode
    1807974
  • Title

    Resonant overvoltages produced in EHV transformer windings due to power system transients

  • Author

    De, A. ; Chakrabarti, A. ; Hazra, P.

  • Author_Institution
    Dept. of Electr. Eng., Bengal Eng. & Sci. Univ., Howrah, India
  • fYear
    2004
  • fDate
    20-22 Dec. 2004
  • Firstpage
    74
  • Lastpage
    77
  • Abstract
    Electrical transients generated in power systems due to switching operations comprise of voltages and currents of complex waveshapes ranging over broad spectrum of frequencies. Such transients when travel through transformers can excite the winding´s natural resonate frequencies. The resulting winding resonance leads in severe internal voltage amplification and abnormal stresses on the insulation. In the present paper the authors have conducted studies to ascertain how the winding insulations of a 400 KV EHV power transformer are stressed when one or more of the winding´s natural frequencies are triggered by power system transients.
  • Keywords
    internal stresses; overvoltage protection; power transformer insulation; power transformer protection; resonance; switching transients; transformer windings; 400 kV; EHV power transformer; abnormal stress; electrical transient generation; internal voltage amplification; natural resonant frequency; power system transient; resonant overvoltage; switching operation; transformer winding insulation; Circuit faults; Power system transients; Power transformer insulation; Power transformers; Resonance; Resonant frequency; Solid modeling; Surges; Voltage-controlled oscillators; Windings;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    India Annual Conference, 2004. Proceedings of the IEEE INDICON 2004. First
  • Print_ISBN
    0-7803-8909-3
  • Type

    conf

  • DOI
    10.1109/INDICO.2004.1497709
  • Filename
    1497709