Abstract :
An objective formulation of the impulse testing procedure is proposed based on models for winding response as well as fault models. Experimental validation of the fault models for breakdown and partial discharge (PD) is provided. A new adaptive filtering approach is proposed for analysis during impulse tests. The procedure is validated with experimental investigation on a 10 section lumped parameter network.
Keywords :
adaptive filters; continuous time filters; impulse testing; lumped parameter networks; partial discharges; power transformer testing; programmable filters; transformer windings; adaptive filtering approach; electric breakdown; fault model; impulse testing procedure; lumped parameter network; partial discharge; programmable continuous time filter; transformer; winding response; Electric breakdown; Filters; Helium; IEC standards; Impulse testing; Insulation testing; Lightning; Partial discharges; Power transformer insulation; Switches;