• DocumentCode
    1810878
  • Title

    Improved architecture for Profinet IRT devices

  • Author

    Felser, C. ; Felser, Max ; Kaghazchi, Hamed

  • fYear
    2012
  • fDate
    17-21 Sept. 2012
  • Firstpage
    1
  • Lastpage
    8
  • Abstract
    This paper deals with Real-Time applications based on Profinet IO Real-Time Class 3. The industrial automation in some cases requires the precision of IO data timing well below the delivered cycle time on the bus. When using the Isochronous Real-Time protocol of Profinet, one single predefined time within a cycle time can be chosen for the inputs- and outputs. The work presented here, shows how the architecture of a Profinet device can be improved. The user can define the time of an input or output within the given time slot with an accuracy of 65 nanoseconds. Furthermore the feasibility of the proposed design is proven with several measurements and simulations.