Performance improvement of harmonic detection using synchronous reference frame method
Author
Santiprapan, P. ; Areerak, K.-L.
Author_Institution
Sch. of Electr. Eng., Suranaree Univ. of Technol. (SUT), Nakhon Ratchasima, Thailand
fYear
2010
fDate
19-20 June 2010
Firstpage
52
Lastpage
55
Abstract
This paper presents the performance improvement of harmonic detection using a synchronous reference frame method (SRF). This method is used with shunt active power filter to eliminate the harmonic in three-phase power system. The cutoff frequency tuning of low pass and high pass filters is included in the process of SRF method. The shunt active power filter model can be represented by the ideal current source. This model is used for testing the performance of harmonic elimination. In this paper, the three-phase diode rectifier behaves as the nonlinear load to generate the harmonic of the system. The simulation results and discussion are described in this paper.
Keywords
active filters; diodes; harmonic generation; high-pass filters; low-pass filters; power harmonic filters; power system harmonics; rectifying circuits; cutoff frequency; harmonic detection; harmonic elimination; harmonic generation; high pass filter; low pass filter; nonlinear load; shunt active power filter; synchronous reference frame method; three-phase diode rectifier; three-phase power system; Educational institutions;
fLanguage
English
Publisher
ieee
Conference_Titel
Advances in Energy Engineering (ICAEE), 2010 International Conference on
Conference_Location
Beijing
Print_ISBN
978-1-4244-7831-6
Type
conf
DOI
10.1109/ICAEE.2010.5557615
Filename
5557615