Dielectric on-site testing of GIL
Author :
Schichler, U. ; Diessne, A. ; Gorablenkow, J.
Author_Institution :
Power Tranmission & Distribution, Siemens AG, xx, Germany
Abstract :
This paper deals with the high voltage on-site testing of GIL. After a description of the general design and insulating system the IEC recommendations for on-site testing are listed. AC testing and tests with impulse voltage are described. The front duration of applied impulse voltage must be adjusted to the length of GIL test sections due to travelling wave phenomena. VFT voltages can be beneficial for testing. The UHF method can be used for PD diagnostics. An example is given for on-site testing of a GIL with a length of 440 m.
Keywords :
IEC standards; SF6 insulation; dielectric materials; gas insulated transmission lines; insulating materials; insulation testing; 440 m; AC testing; PD diagnostics; SF6; SF6 insulation; UHF method; dielectrics; gas insulation lines testing; insulating system design; travelling wave phenomena; very fast transient voltages; Conductors; Dielectrics and electrical insulation; Gas insulated transmission lines; Gas insulation; Geographic Information Systems; Impulse testing; Insulation testing; Power transformer insulation; System testing; Voltage;