DocumentCode
1818550
Title
Electrical insulation performance in Air gap with covered electrode
Author
Mizuno, T. ; Morita, K. ; Kurata, Y. ; Nagatake, K. ; Saitoh, H.
Author_Institution
Core Technol. Res. Dept., Meidensha Corp., Tokyo, Japan
Volume
1
fYear
2003
fDate
1-5 June 2003
Firstpage
133
Abstract
The electrical performance of Air insulated system could be improved by composite gas/polymer insulation. Covered hemisphere-rod and plane electrode has been applied in our study with the purpose of investigating the effect of composite insulated system for an application of switchgears. Therefore the aim of this study was to investigate the characteristics of covered length in addition to covered thickness. The results indicated that the effect of covered length was obtained in case of using thinner covered electrode. Moreover, impulse partial discharge light emission image was observed in order to reveal the process from partial discharge inception to breakdown. The result indicated that partial discharge inception occurred on the tip of covered electrode, and that the polarity difference of the process diversified the effect of covered length.
Keywords
air gaps; composite insulating materials; electrodes; gas insulated switchgear; partial discharges; air gap; air insulated system; composite insulated system; electrical insulation; electrode; impulse partial discharge light emission image; polarity difference; switchgears application; Breakdown voltage; Dielectrics and electrical insulation; Electric breakdown; Electrodes; Gas insulation; Laboratories; Partial discharges; Power systems; Power transformer insulation; Testing;
fLanguage
English
Publisher
ieee
Conference_Titel
Properties and Applications of Dielectric Materials, 2003. Proceedings of the 7th International Conference on
ISSN
1081-7735
Print_ISBN
0-7803-7725-7
Type
conf
DOI
10.1109/ICPADM.2003.1218371
Filename
1218371
Link To Document