DocumentCode :
1818954
Title :
Electroluminescence for XLPE cable diagnosis
Author :
Ishii, R. ; Iemura, S. ; Kubo, M. ; Nagura, N. ; Shimizu, N.
Author_Institution :
Kansai Electr. Power Co., Inc., Hyogo, Japan
Volume :
1
fYear :
2003
fDate :
1-5 June 2003
Firstpage :
199
Abstract :
Electrical treeing is responsible for the breakdown of power cables with polymeric insulation, such as low density polyethylene (LDPE) and cross-linked polyethylene (XLPE). Electroluminescence (EL) occurs in the initiation phase of electrical tree. We studied the characteristics of EL in XLPE cut from 77 kV class power cables. We found that EL intensity in XLPE cut from removed cable gradually decreases with voltage application time compared with that in unaged XLPE. This tendency is considered to reflect the degradation in XLPE.
Keywords :
XLPE insulation; electric breakdown; electroluminescence; organic insulating materials; power cable insulation; trees (electrical); LDPE; XLPE cable diagnosis; XLPE degradation; breakdown; cross-linked polyethylene; electrical tree; electroluminescence; low density polyethylene; polymeric insulation; Cable insulation; Dielectrics and electrical insulation; Electric breakdown; Electroluminescence; Plastic insulation; Polyethylene; Polymers; Power cables; Trees - insulation; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Properties and Applications of Dielectric Materials, 2003. Proceedings of the 7th International Conference on
ISSN :
1081-7735
Print_ISBN :
0-7803-7725-7
Type :
conf
DOI :
10.1109/ICPADM.2003.1218387
Filename :
1218387
Link To Document :
بازگشت