• DocumentCode
    1821567
  • Title

    Decay characteristics of residual dc voltage for 1000 kV GIS

  • Author

    Yamagata, Y. ; Rokunohe, T. ; Endou, F.

  • Author_Institution
    Tokyo Electr. Power Co., Chiyoda-Ku, Japan
  • Volume
    2
  • fYear
    2003
  • fDate
    1-5 June 2003
  • Firstpage
    614
  • Abstract
    Volume and surface resistivity are varied by temperature and electric field strength of an insulator. As change of the insulator electric field strength is very small during residual dc voltage measurement, insulator resistivity depends on temperature. So insulator resistivity is estimated by fundamental characteristics of resistivity as a function of temperature. Then the decay time constant of residual dc voltage for l000 kV GIS is calculated by resistivity based on the calculated insulator resistance for the temperature. Finally the measured decay time constant is compared with the calculated one.
  • Keywords
    electric strength; electrical resistivity; gas insulated substations; gas insulated switchgear; 1000 kV; GIS; decay time constant; insulator electric field strength; insulator resistivity; surface resistivity; Computational Intelligence Society; Conductivity; Dielectrics and electrical insulation; Electrodes; Geographic Information Systems; Prototypes; Surges; Temperature; Testing; Voltage measurement;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Properties and Applications of Dielectric Materials, 2003. Proceedings of the 7th International Conference on
  • ISSN
    1081-7735
  • Print_ISBN
    0-7803-7725-7
  • Type

    conf

  • DOI
    10.1109/ICPADM.2003.1218492
  • Filename
    1218492