DocumentCode :
1823607
Title :
Windowed standard deviation-based transient feature extraction for earth fault protection in MV networks
Author :
Elkalashy, Nagy I. ; Elhaffar, Abdelsalam M. ; Abdel-Fattah, Mohamed F. ; Lehtonen, M. ; Tarhuni, Naser G.
Author_Institution :
Helsinki Univ. of Technol. (TKK), Espoo, Finland
fYear :
2009
fDate :
1-4 Sept. 2009
Firstpage :
1
Lastpage :
4
Abstract :
In this paper, the windowed standard deviation (WSTD) is used to extract the initial transients created in residual current waveforms generated due to earth faults in medium voltage (MV) compensated networks. The sliding window width used for computing the standard deviation is evaluated from the frequency filter point of view. The fault cases occurring in a compensated 20 kV network are simulated by ATP/EMTP concerning practical fault case such as arcing faults. Results provide evidence that the windowed standard deviation can be used to extract initial transients although they are non-stationary sinusoidal signals.
Keywords :
earthing; fault diagnosis; feature extraction; filtering theory; power distribution protection; transient analysis; ATP/EMTP; MV network fault protection; earth fault protection; frequency filter; medium voltage compensated networks; nonstationary sinusoidal signals; residual current waveforms; sliding window width; voltage 20 kV; windowed standard deviation-based transient feature extraction; Communication system control; Earth; Feature extraction; Frequency response; Home appliances; Protection; Samarium; Switches; Temperature control; Wind energy generation; Earth fault; initial transients; residual currents; windowed standard deviation;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Universities Power Engineering Conference (UPEC), 2009 Proceedings of the 44th International
Conference_Location :