DocumentCode :
1832244
Title :
HEMP field coupling with buried power distribution cables
Author :
Sunitha, K. ; Thomas, M. Joy
Author_Institution :
Dept. of Electr. Eng., Indian Inst. of Sci., Bangalore, India
fYear :
2009
fDate :
17-21 Aug. 2009
Firstpage :
220
Lastpage :
225
Abstract :
The interaction of transient electromagnetic field due to HEMP with multicore buried power distribution cables is studied in this paper. Using transmission line analysis, the induced current on the shield of the cable is computed. The cable transfer impedance is used to find the coupled current in the inner circuit. The variation of the current induced on the inner conductor as a function of the distance along the length of the cable is computed. The influence of the depth of burial of the cable on the induced current is evaluated to determine the soil attenuation effects.
Keywords :
electromagnetic coupling; electromagnetic fields; electromagnetic pulse; power cables; power distribution; underground cables; HEMP field coupling; cable transfer impedance; inner conductor; multicore buried power distribution cables; nuclear electromagnetic pulses; soil attenuation effects; transient electromagnetic field; transmission line analysis; underground cables; Cables; Couplings; Distributed parameter circuits; Electromagnetic fields; Electromagnetic transients; Impedance; Multicore processing; Power distribution; Power system transients; Power transmission lines;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electromagnetic Compatibility, 2009. EMC 2009. IEEE International Symposium on
Conference_Location :
Austin, TX
Print_ISBN :
978-1-4244-4266-9
Electronic_ISBN :
978-1-4244-4058-0
Type :
conf
DOI :
10.1109/ISEMC.2009.5284570
Filename :
5284570
Link To Document :
بازگشت