• DocumentCode
    1859693
  • Title

    Experimental evaluation of current transformer performance under saturation

  • Author

    Chawande, Pradeep ; Soman, S.A. ; Apte, P.R. ; Pandit, Shubha

  • Author_Institution
    Indian Inst. of Technol., Mumbai
  • fYear
    2005
  • fDate
    Nov. 29 2005-Dec. 2 2005
  • Firstpage
    1
  • Lastpage
    75
  • Abstract
    Current transformers form an integral part of protective systems. Ideal current transformers (CTs) are expected to reproduce the primary current faithfully on the secondary side. Often, during fault conditions an important component of current is exponentially decaying DC offset current. Under such conditions the CT saturates, and hence it cannot reproduce the primary current faithfully. This paper deals with experimental methods for determining CT performance under saturation. A laboratory setup has been developed to observe CT response under steady state and fault conditions. Thus, it is now possible to experimentally evaluate the CT performance under fault conditions
  • Keywords
    current transformers; electrical faults; power transformer protection; current transformer; exponentially decaying DC offset current; fault conditions; protective systems; saturation; Circuit faults; Current transformers; Fault currents; Laboratories; Power system relaying; Protection; Protective relaying; Relays; Signal generators; Testing; CT Saturation; Education; Power System Protection;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Engineering Conference, 2005. IPEC 2005. The 7th International
  • Conference_Location
    Singapore
  • Print_ISBN
    981-05-5702-7
  • Type

    conf

  • DOI
    10.1109/IPEC.2005.206882
  • Filename
    1627171