Title :
Flashover behaviour of converter transformer insulation subjected to superimposed ac and dc voltages
Author :
Ram, S. S Tulasi ; Kamaraju, V. ; Singh, B.P.
Author_Institution :
Dept. of Electr. Eng., JNTU Coll. of Eng., Kakinada, India
Abstract :
In HVDC application, the interdisc winding insulation of a converter transformer is subjected to superimposed AC and DC voltages. Therefore, a knowledge of the behaviour of such an insulation system subjected to AC, DC and superimposed AC and DC voltages is essential. In order to simulate similar conditions in the interdisc insulation system, experiments are conducted with both oil and oil-spacer insulation systems. In general, the important factors, which influence the breakdown phenomena with these voltages are, field enhancement, charged particles, dielectric mismatch, space charges and surface charging of the interface
Keywords :
flashover; HVDC application; breakdown phenomena; charged particles; converter transformer insulation; dielectric mismatch; field enhancement; flashover behaviour; interdisc winding insulation; oil insulation systems; oil-spacer insulation systems; space charges; superimposed AC voltages; superimposed DC voltages; surface charging; Analog-digital conversion; Breakdown voltage; Dielectric breakdown; Dielectrics and electrical insulation; Flashover; HVDC transmission; Oil insulation; Petroleum; Power transformer insulation; Space charge;
Conference_Titel :
Electrical Insulation and Dielectric Phenomena, 1994., IEEE 1994 Annual Report., Conference on
Conference_Location :
Arlington, TX
Print_ISBN :
0-7803-1950-8
DOI :
10.1109/CEIDP.1994.592068