DocumentCode
1864239
Title
A new control strategy for three-phase shunt active power filter that based on source instantaneous power
Author
Riyadi, S. ; Haroen, Y.
Author_Institution
Dept. of Electr. Eng., Socgijapranata Catholic Univ., Semarang
fYear
2005
fDate
Nov. 29 2005-Dec. 2 2005
Firstpage
991
Abstract
This paper proposes a new control strategy for three-phase shunt active power filter that is capable to operate under three-wire or four-wire systems. It is based on source instantaneous power. The principle of this control method is to eliminate undesired source currents. Calculation of source instantaneous power is needed to determine instantaneous power component that may not be created by the source. This calculation only needs source currents and phase information so the amount of sensors can be minimized. This control method can force source currents nearly sinusoidal and have unity power factor. Application in four-wire system will reduce neutral current at source side. Simulation is done to verify analysis
Keywords
active filters; power filters; four-wire systems; neutral current reduction; source instantaneous power; three-phase shunt active power filter; three-wire systems; undesired source currents elimination; unity power factor; Active filters; Control systems; Force control; Impedance; Power filters; Power harmonic filters; Power system harmonics; Power system simulation; Pulse width modulation converters; Reactive power; active power filter (APF); instantaneous reactive power; instantaneous real power;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Engineering Conference, 2005. IPEC 2005. The 7th International
Conference_Location
Singapore
Print_ISBN
981-05-5702-7
Type
conf
DOI
10.1109/IPEC.2005.207052