• DocumentCode
    1865213
  • Title

    Facts based fault current limiter utilization in HV grid

  • Author

    Golshani, Amir ; Khakpour, A. ; Hofmann, Lutz

  • Author_Institution
    Dept. of Electr. Eng., K.N.T. Univ. of Technol., Tehran, Iran
  • fYear
    2012
  • fDate
    April 29 2012-May 2 2012
  • Firstpage
    1
  • Lastpage
    6
  • Abstract
    Future´s load and generation model of Tehran power network depicts fast increase in demand and development of power network. By 2015, Two new generating stations are expected to be installed which result in the increase of short-circuit capacity of a few substations in excess of the interrupting rating of exiting circuit breakers. This paper intends to analyze the consequences of employing thyristor protected series capacitor (TPSC) based short-circuit current limiter (SCCL) in Tehran power grid. Short-circuit, transient stability and transient recovery voltage studies were carried out by using DIgSILENT and EMTP softwares. The results demonstrate that SCCL installation can reduce fault current level in four substations of Tehran power network and improve transient stability margins. On the other hand, rate of rise of recovery voltage across some circuit breakers will exceed the value specified in standard which can be coped with by adding extra capacitor.
  • Keywords
    circuit breakers; electric power generation; fault current limiters; flexible AC transmission systems; power capacitors; power grids; power system transient stability; power transmission protection; power utilisation; short-circuit currents; substations; thyristor applications; DIgSILENT software; EMTP software; FACTS based fault current limiter utilization; HV grid; SCCL; TPSC; Tehran power grid network; circuit breaker; generation model; load model; short-circuit current limiter; substation; thyristor protected series capacitor; transient recovery voltage; transient stability margin; Circuit breakers; Circuit faults; Power system stability; Stability analysis; Substations; Transient analysis; FACTs; TRV; fault current limiter; short-circuit; transient stability;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical & Computer Engineering (CCECE), 2012 25th IEEE Canadian Conference on
  • Conference_Location
    Montreal, QC
  • ISSN
    0840-7789
  • Print_ISBN
    978-1-4673-1431-2
  • Electronic_ISBN
    0840-7789
  • Type

    conf

  • DOI
    10.1109/CCECE.2012.6334818
  • Filename
    6334818