DocumentCode
1869049
Title
Voltage dips cause problems with digital flickermeters
Author
Koponen, P. ; Mäkinen, A. ; Seesvuori, R.
Author_Institution
VTT Energy, Espoo, Finland
Volume
1
fYear
2001
fDate
2001
Abstract
Digital flickermeters often indicate flicker levels that are inconsistent with each other or too high compared with visual observations. In order to learn the reasons for this, some power quality analysers that include flicker measurements were compared in laboratory tests. Also the flicker measurement method of the IEC 61000-4-15 standard was simulated. It showed that even very short voltage dips and interruptions cause inconsistent and very high readings in the compared meters. In the simulations it was possible to remove the problem by limiting the internal variables of the method to a small range. The standard does not define the range of these internal variables but describes flickermeters with analogue filters. Later digital implementation enabled large variable ranges, which led to increased sensitivity to dips. The readings of the compared digital flickermeters are rather misleading in the presence of voltage dips and interruptions. Solutions to this problem are considered
Keywords
IEC standards; digital instrumentation; electric noise measurement; power supply quality; power system measurement; IEC 61000-4-15; analogue filters; digital flickermeters; flicker measurements; laboratory tests; power quality; power quality analysers; very short voltage dips; very short voltage interruptions; voltage dips; Electronics packaging; IEC standards; Laboratories; Measurement standards; Monitoring; Pollution measurement; Power measurement; Power quality; Testing; Voltage fluctuations;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Tech Proceedings, 2001 IEEE Porto
Conference_Location
Porto
Print_ISBN
0-7803-7139-9
Type
conf
DOI
10.1109/PTC.2001.964612
Filename
964612
Link To Document