DocumentCode :
18744
Title :
Development of Full Frequency Bandwidth Measurement of VFTO in UHV GIS
Author :
Yue Gongchang ; Liu Weidong ; Chen Weijiang ; Guan Yonggang ; Li Zhibing
Author_Institution :
Dept. of Electr. Eng., Tsinghua Univ., Beijing, China
Volume :
28
Issue :
4
fYear :
2013
fDate :
Oct. 2013
Firstpage :
2550
Lastpage :
2557
Abstract :
In order to study the characteristics of very fast transient overvoltage (VFTO) in ultra-high voltage (UHV) gas-insulated switchgear (GIS), the authors have developed a full frequency bandwidth measurement system based on a porthole-type capacitive voltage divider. Three kinds of measurement circuits for the measurement system are studied and the influence of cable length on measurement results is analyzed in this paper. The calibration of the measurement system using step response was conducted. The results show that the measurement system of the capacitive voltage divider integrated with an impedance converter has a bandwidth ranging from 0.003 Hz to 300 MHz at least. It can be used to measure the full VFTO during DS operation perfectly. A full-scale UHV DS (disconnect switchgear) is used to establish the test circuit. The measurement system with good anti-electromagnetic interference ability was constructed. Four different measurement locations are chosen on which to install the measurement system. An approximate total of 3000 closing and opening operation tests were conducted. Due to the wide frequency band of the measurement system, it is possible to obtain the full VFTO waveform accurately and conveniently. According to the waveforms, the key parameters of VFTO, such as trapped charge voltage, peak value of VFTO, breakdown characteristic of DS, frequency spectrum of transient waveform, and the overvoltage coefficient could be obtained.
Keywords :
electric breakdown; gas insulated switchgear; impedance convertors; overvoltage; voltage dividers; voltage measurement; UHV GIS; VFTO; breakdown characteristic; disconnect switchgear; frequency 0.003 MHz to 300 MHz; full frequency bandwidth measurement; impedance converter; measurement circuit; measurement system calibration; overvoltage coefficient; porthole type capacitive voltage divider; transient waveform frequency spectrum; ultra high voltage gas insulated switchgear; very fast transient overvoltage; Frequency measurement; Impedance matching; Measurement; Switchgear; Transient analysis; Breakdown characteristic; cable length; capacitive voltage divider; full bandwidth measurement of VFTO; impedance converter; overvoltage coefficient; peak value of VFTO; trapped charge voltage; ultra-high voltage gas-insulated switchgear;
fLanguage :
English
Journal_Title :
Power Delivery, IEEE Transactions on
Publisher :
ieee
ISSN :
0885-8977
Type :
jour
DOI :
10.1109/TPWRD.2013.2267781
Filename :
6550900
Link To Document :
بازگشت