Problems of voltage transducer in harmonic measurement
Author
Yao, Xiao ; Bin, Hu ; Chunnian, Deng
Author_Institution
Hubei Electr. Power Test & Res. Inst., Wuhan, China
Volume
1
fYear
2002
fDate
6-9 Oct. 2002
Firstpage
33
Abstract
Capacitive voltage transformer (CVT) in high and medium voltage system cannot be used for harmonic voltage measurement. A new method making use of capacitive taps in current transformer (CT) bushings is recommended here, this method can achieve the good precision of harmonic voltage measurement. Attention to potential transformer (PT) should be paid in special cases such as a resistor or nonlinear resistor is connected across the neutral point on primary side and ground. In such a case, the harmonic voltage measurement cannot reflect the real distortion of the system voltage.
Keywords
bushings; current transformers; potential transformers; power system harmonics; resistors; transducers; voltage measurement; CT; CVT; PT; capacitive taps; capacitive voltage transformer; current transformer bushings; harmonic voltage measurement; neutral point; potential transformer; system voltage; voltage transducer; Aluminum; Current transformers; Frequency; Insulators; Medium voltage; Power system harmonics; Resistors; Transducers; Voltage measurement; Voltage transformers;