    Problems of voltage transducer in harmonic measurement

  • Author

    Yao, Xiao ; Bin, Hu ; Chunnian, Deng

  • Author_Institution
    Hubei Electr. Power Test & Res. Inst., Wuhan, China
  • Volume
    1
  • fYear
    2002
  • fDate
    6-9 Oct. 2002
  • Firstpage
    33
  • Abstract
    Capacitive voltage transformer (CVT) in high and medium voltage system cannot be used for harmonic voltage measurement. A new method making use of capacitive taps in current transformer (CT) bushings is recommended here, this method can achieve the good precision of harmonic voltage measurement. Attention to potential transformer (PT) should be paid in special cases such as a resistor or nonlinear resistor is connected across the neutral point on primary side and ground. In such a case, the harmonic voltage measurement cannot reflect the real distortion of the system voltage.
  • Keywords
    bushings; current transformers; potential transformers; power system harmonics; resistors; transducers; voltage measurement; CT; CVT; PT; capacitive taps; capacitive voltage transformer; current transformer bushings; harmonic voltage measurement; neutral point; potential transformer; system voltage; voltage transducer; Aluminum; Current transformers; Frequency; Insulators; Medium voltage; Power system harmonics; Resistors; Transducers; Voltage measurement; Voltage transformers;