DocumentCode :
1876548
Title :
Harmonic filter design by the attenuation factor method
Author :
Sainz, L.
Author_Institution :
Dept. of Electr. Eng., Univ. Politecnica de Catalunya, Barcelona, Spain
Volume :
2
fYear :
2002
fDate :
6-9 Oct. 2002
Firstpage :
513
Abstract :
There are different methods of filter design to calculate its kVA rated power and voltage distortion. The attenuation factor method is a simple but effective procedure presented in the bibliography to characterise harmonic distortion. The present paper expands this method to include an analysis of buses with capacitor banks and linear loads. Attenuation of harmonic voltages by filters is calculated with the expanded procedure and presented in the form of generalised curves. This procedure is applied to a filter design example and compared with the original one.
Keywords :
distribution networks; harmonic distortion; load flow; power capacitors; power harmonic filters; static VAr compensators; attenuation factor method; bus analysis; capacitor bank; harmonic distortion; harmonic filter design; kVA rated power calculation; linear loads; voltage distortion calculation; Attenuation; Bibliographies; Capacitors; Hafnium; Harmonic distortion; Impedance; Power harmonic filters; Power system harmonics; Total harmonic distortion; Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Harmonics and Quality of Power, 2002. 10th International Conference on
Print_ISBN :
0-7803-7671-4
Type :
conf
DOI :
10.1109/ICHQP.2002.1221488
Filename :
1221488
Link To Document :
بازگشت