DocumentCode :
1877167
Title :
Bus charging current switching in GIS by disconnector
Author :
Bojic, P.
Author_Institution :
Ansaldo T&D, Genoa, Italy
Volume :
3
fYear :
2001
fDate :
2001
Abstract :
This paper presents results of the bus charging current switching test performed on disconnector of 300 kV gas insulated metal enclosed switchgear (GIS). Internal effects which occurred during the making and breaking operation are explained from the design point of view, characteristics required by standards are presented, main parameters of switchgear, design feature and tests results of disconnector are given and discussed. A low speed disconnector with additionally shaped screens is proposed as an optimal solution regarding values of pre-arcing and arcing times as criteria of wearing off of contacts and screens and reliability in service
Keywords :
gas insulated switchgear; switching; 300 kV; GIS; arcing times; bus charging current switching; contacts wear; disconnectors; gas insulated metal enclosed switchgear; internal effects; pre-arcing times; switchgear; Earth; Gas insulation; Geographic Information Systems; Grounding; Performance evaluation; Substations; Switches; Switchgear; Testing; Voltage control;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power Tech Proceedings, 2001 IEEE Porto
Conference_Location :
Porto
Print_ISBN :
0-7803-7139-9
Type :
conf
DOI :
10.1109/PTC.2001.964943
Filename :
964943
Link To Document :
بازگشت