DocumentCode
1878909
Title
Proper lightning arrester application improves distribution system reliability
Author
Mackevich, J.P.
Author_Institution
Raychem Corp., Menlo Park, CA, USA
fYear
1993
fDate
7-10 Dec 1993
Firstpage
153
Abstract
For distribution system overvoltage protection design, all necessary sources of contribution to net residual voltage may not be considered, overstating the actual margins of protection available. This includes total lead length and current impulse rate-of-rise. Underground circuits are subject to voltage doubling. If all sources of residual voltage are not considered, the calculated margin will be overstated as well. Recommendations for improved protection are included, and various examples of protection for an 11 kV, 95 kV basic impulse insulation level system are included
Keywords
distribution networks; lightning protection; overvoltage protection; power system protection; power system reliability; surge protection; 11 kV; cable protection; current impulse rate-of-rise; distribution system reliability; gapless lightning arrester; lightning arrester application; net residual voltage; overvoltage protection; protection margin; spark gaps; switchgear protection; underground circuits; voltage doubling;
fLanguage
English
Publisher
iet
Conference_Titel
Advances in Power System Control, Operation and Management, 1993. APSCOM-93., 2nd International Conference on
Conference_Location
IET
Print_ISBN
0-85296-569-9
Type
conf
Filename
292705
Link To Document