• DocumentCode
    1878909
  • Title

    Proper lightning arrester application improves distribution system reliability

  • Author

    Mackevich, J.P.

  • Author_Institution
    Raychem Corp., Menlo Park, CA, USA
  • fYear
    1993
  • fDate
    7-10 Dec 1993
  • Firstpage
    153
  • Abstract
    For distribution system overvoltage protection design, all necessary sources of contribution to net residual voltage may not be considered, overstating the actual margins of protection available. This includes total lead length and current impulse rate-of-rise. Underground circuits are subject to voltage doubling. If all sources of residual voltage are not considered, the calculated margin will be overstated as well. Recommendations for improved protection are included, and various examples of protection for an 11 kV, 95 kV basic impulse insulation level system are included
  • Keywords
    distribution networks; lightning protection; overvoltage protection; power system protection; power system reliability; surge protection; 11 kV; cable protection; current impulse rate-of-rise; distribution system reliability; gapless lightning arrester; lightning arrester application; net residual voltage; overvoltage protection; protection margin; spark gaps; switchgear protection; underground circuits; voltage doubling;
  • fLanguage
    English
  • Publisher
    iet
  • Conference_Titel
    Advances in Power System Control, Operation and Management, 1993. APSCOM-93., 2nd International Conference on
  • Conference_Location
    IET
  • Print_ISBN
    0-85296-569-9
  • Type

    conf

  • Filename
    292705