DocumentCode :
1882906
Title :
Protection and commissioning of multifunction digital transformer relays at medium voltage industrial facilities
Author :
Mozina, Charles J.
Author_Institution :
Beckwith Electr. Co. Inc., Largo, FL
fYear :
2005
fDate :
23-23 June 2005
Firstpage :
265
Lastpage :
275
Abstract :
The application of multifunction digital relays to protect medium voltage power transformers has become a common industrial practice. Industrial transformers, unlike utility transformers, frequently use neutral grounding resistors to limit ground current during faults to a 200-400 A level on medium voltage systems. This paper will discuss why these types of transformers require sensitive ground differential protection. The paper will also discuss the basics of transformer protection including: phasing standards, through-fault withstand capability, differential/fusing/ overcurrent protection, slope, CT requirements, harmonic restraint, and communicating these properly to new digital relays. The rationale for providing transformer overexcitation protection on all major transformers within mill facilities is also addressed. Advancements in digital technology have allowed relay manufacturers to include more and more relay functions within a single hardware platform as well as address increasingly more transformer winding configurations. This has resulted in digital transformer relays requiring an Einstein to set and an Edison to commission. Since there are few Einsteins or Edisons among us, the next generation of transformer relays needs to concentrate on this complexity issue in addition to technical improvements. This paper addresses these issues that the author believes are the major shortcomings of existing digital transformer protective relays
Keywords :
ANSI standards; IEC standards; commissioning; current transformers; earthing; overcurrent protection; power transformer protection; relay protection; transformer windings; ANSI; CT requirement; E-M relay; IEC standards; differential-fusing-overcurrent protection; digital transformer relay protection; electrical commissioning; fault withstand capability; ground current; ground differential protection; harmonic restraint; industrial transformer; medium voltage power transformer; multifunction digital relay; neutral grounding resistor; phasing standard; relay manufacturer; transformer overexcitation protection; transformer winding; Digital relays; Electrical equipment industry; Grounding; Industrial plants; Medium voltage; Power system protection; Power system relaying; Power transformers; Protective relaying; Resistors;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Pulp and Paper Industry Technical Conference, 2005. Conference Record of 2005 Annual
Conference_Location :
Jacksonville, FL
Print_ISBN :
0-7803-9089-X
Type :
conf
DOI :
10.1109/PAPCON.2005.1502074
Filename :
1502074
Link To Document :
بازگشت