    Data center characteristic temperature signatures and SHI correlation to nondimensional parameters

  • Author

    Sergio, Escobar ; Ratnesh, Sharma

  • Author_Institution
    Hewlett-Packard, Palo Alto, CA
  • fYear
    2008
  • fDate
    28-31 May 2008
  • Firstpage
    1203
  • Lastpage
    1209
  • Abstract
    Design of high power data center with cost effective reliable cooling solutions is essential for reliability. Over designed cooling systems and rack layouts allowing mixing of air streams increase the energy consumption and cost of data centers. Air current mixing is a factor to control when looking to improve the thermal cooling performance in large data centers. In this work, real time temperature data is collected from sensors located at the input and output of racks. Data collected reveal consistent temperature signatures. Temperature signature trends provide an insight of the mixing of hot and cool air streams in the data center. Uniform temperature trends indicate balanced regions within data center that are not perturbed by variations in air currents. Linear temperatures with monotonic variation are indicative of gradual mixing of hot and cold air in the input region of racks. Presence of pockets of hot or cold air is manifested as "u" shape trends. They are symptomatic of larger flow reversals occurring in the input region in front of racks, with great potential of reducing the coefficient of performance of data centers. The slope temperature in any temperature trend is another indication of the air mixing degree. The supply heat index (SHI) related to the degree of mixing is correlated to parameters of the data center. A nondimensional parameter G is defined in function of Eckert and Reynolds number. G shows a strong linear correlation with SHI for row of racks and a more scattered relation for single racks. G may be used as a first approximation to predict the cooling performance of a data center.
  • Keywords
    thermal management (packaging); Eckert number; Reynolds number; SHI correlation; cooling solutions; high power data center; monotonic variation; nondimensional parameters; rack layouts; supply heat index; temperature signatures; thermal cooling performance; Cooling; Costs; Fluid dynamics; Heat transfer; Load flow; Load flow analysis; Power system reliability; Temperature sensors; Thermal conductivity; Thermal management; air mixing; dimensionless parameters; rack layout; thermal management;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Thermal and Thermomechanical Phenomena in Electronic Systems, 2008. ITHERM 2008. 11th Intersociety Conference on
  • Conference_Location
    Orlando, FL
  • ISSN
    1087-9870
  • Print_ISBN
    978-1-4244-1700-1
  • Electronic_ISBN
    1087-9870
  • Type

    conf

  • DOI
    10.1109/ITHERM.2008.4544398
  • Filename
    4544398