Title :
Optimal Placement and Sizing Method to Improve the Voltage Stability Margin in a Distribution System Using Distributed Generation
Author :
Al Abri, R.S. ; El-Saadany, Ehab F. ; Atwa, Yasser M.
Author_Institution :
Dept. of Electr. & Comput. Eng., Univ. of Waterloo, Waterloo, ON, Canada
Abstract :
Recently, integration of distributed generation (DG) in distribution systems has increased to high penetration levels. The impact of DG units on the voltage stability margins has become significant. Optimization techniques are tools which can be used to locate and size the DG units in the system, so as to utilize these units optimally within certain limits and constraints. Thus, the impacts of DG units issues, such as voltage stability and voltage profile, can be analyzed effectively. The ultimate goal of this paper is to propose a method of locating and sizing DG units so as to improve the voltage stability margin. The load and renewable DG generation probabilistic nature are considered in this study. The proposed method starts by selecting candidate buses into which to install the DG units on the system, prioritizing buses which are sensitive to voltage profile and thus improve the voltage stability margin. The DG units´ placement and sizing is formulated using mixed-integer nonlinear programming, with an objective function of improving the stability margin; the constraints are the system voltage limits, feeders´ capacity, and the DG penetration level.
Keywords :
distributed power generation; integer programming; nonlinear programming; power distribution; DG unit placement; DG units; distributed generation; distribution system; high penetration levels; mixed-integer nonlinear programming; optimal placement method; optimal sizing method; optimization techniques; renewable DG generation probabilistic nature; voltage profile; voltage stability margin; Load modeling; Power system stability; Reactive power; Stability criteria; Wind turbines; Distributed generation (DG); distribution system; optimum power flow; voltage profile; voltage stability;
Journal_Title :
Power Systems, IEEE Transactions on
DOI :
10.1109/TPWRS.2012.2200049