• DocumentCode
    1896023
  • Title

    In service turbine generators stator windings failure risks minimization on the base of discharge events on-line monitoring

  • Author

    Aksenov, Y.P.

  • Author_Institution
    DIACS Moscow, Russia
  • fYear
    2001
  • fDate
    2001
  • Firstpage
    429
  • Lastpage
    436
  • Abstract
    Results of the on-line insulation diagnostic of turbine generators are provided. Measures taken to ensure the reliability of 1000, 500, 220, 120 and 60 MVA generators are discussed. Features of faults that occurred in the various types of insulation are given. Results of the partial discharge locations using off-line diagnostics are provided. The approach for stator windings failure risks minimization has been demonstrated to be successful without subsequent failure: (i) about 70 turbine generators with no defects; (ii) 4 machines with arcing in core; (iii) 6 machines with slot discharges; and (iv) 15 with different insulation
  • Keywords
    computerised monitoring; failure analysis; partial discharge measurement; risk management; stators; turbogenerators; 60 to 1000 MVA; PD Sensor; arcing; insulation defects; insulation faults; noise rejection methods; off-line diagnostics; on-line insulation diagnostic; on-line monitoring; partial discharge locations; reliability; risks minimization; slot discharges; stator windings failure; turbine generators; visual inspection; Computer displays; Condition monitoring; Electromagnetic interference; Insulation; Partial discharge measurement; Partial discharges; Pulse measurements; Risk management; Stator windings; Turbines;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation Conference and Electrical Manufacturing & Coil Winding Conference, 2001. Proceedings
  • Conference_Location
    Cincinnati, OH
  • ISSN
    0362-2479
  • Print_ISBN
    0-7803-7180-1
  • Type

    conf

  • DOI
    10.1109/EEIC.2001.965724
  • Filename
    965724