• DocumentCode
    1904602
  • Title

    Complete relay protection of multi-string fuseless capacitor banks

  • Author

    Fendrick, Leo ; Day, Tim ; Fender, Karl ; McCall, Jack ; Chaudhary, Arvind

  • Author_Institution
    Lincoln Electr. Syst., NE, USA
  • fYear
    2002
  • fDate
    17-21 June 2002
  • Firstpage
    194
  • Lastpage
    198
  • Abstract
    The trend towards large fuseless shunt capacitor banks being employed in power systems is due to the lower cost, compact design, higher reliability with less exposed live parts, and lower losses. This paper describes a novel application of the impedance method to provide complete bank protection by measuring the impedance of each series string of the capacitor bank. The scheme can identify the string(s) with an alarm or trip condition, keep the bank in service with pack failures in multiple strings, and only trip when the bank is actually in an unacceptable operating condition. Because this scheme can account for the distributed failure of packs in strings, bank availability can be increased.
  • Keywords
    capacitor storage; electric impedance measurement; relay protection; capacitor bank protection; complete relay protection; distributed failure; higher reliability; impedance measurement; impedance method; losses; multi-string fuseless capacitor banks; multiple strings; pack failures; relay protection; unacceptable operating condition; Capacitors; Circuit breakers; Fuses; Impedance measurement; Power system protection; Power system reliability; Power systems; Protective relaying; Senior members; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Pulp and Paper Industry Technical Conference, 2002. Conference Record of the 2002 Annual
  • Conference_Location
    Toronto, Ontario, Canada
  • Print_ISBN
    0-7803-7446-0
  • Type

    conf

  • DOI
    10.1109/PAPCON.2002.1015154
  • Filename
    1015154